APAX-5070_15 Datasheet, PDF (1/1 Pages) Advantech Co., Ltd. – Modbus/TCP Communication Coupler | |||
|
APAX-5070
APAX-5072
APAX-5071
Modbus/TCP Communication Coupler
EtherNet/IP Communication Coupler
PROFINET Communication Coupler
APAX-5070
RoHS
COMPLIANT
2002/95/EC
APAX-5072
RoHS
COMPLIANT
2002/95/EC
APAX-5071
RoHS
COMPLIANT
2002/95/EC
Specifications
Specifications
Specifications
General
ÂÂ Certification
CE, FCC class A
ÂÂ Dimensions
30 x 139 x 100 mm
(W x H x D)
ÂÂ Enclosure
ABS+PC
ÂÂ Weight
190 g
ÂÂ Connector
2 x RJ-45 (2-channel
switch, share same IP
address)
ÂÂ Power Consumption 2 W @ 5 VDC (typical)
Communication
ÂÂ Protocol
Modbus/TCP
ÂÂ Connected I/O
32 (max.)*
Modules
ÂÂ Digital Signals
768 (max.)
ÂÂ Analog Signals
192 (max.)
ÂÂ Data Transfer Rates 10/100 Mbps
ÂÂ Topology
Line or star
ÂÂ Isolation Protection 1,500 VAC
Environment
ÂÂ Operating
-10 ~ 60°C
Temperature
(mounted vertically)
 Storage Temperature -40 ~ 85°C
ÂÂ Relative Humidity 5 ~ 95% (non-condensing)
ÂÂ Shock Protection 10 G @ wall mount, half
sine, 11 ms (Confirms to
IEC 60068-2-27)
ÂÂ Vibration Protection 1 Grms @ 5 ~ 500 Hz
(Random, operating, 1 hr/
axis)
2 G @ 5 ~ 500 Hz (Sine,
non-operating, 1 hr/axis)
(Confirms to IEC 60068-2-
64 and IEC 60068-2-6)
Ordering Information
ÂÂ APAX-5070
Modbus/TCP
Communication Coupler
General
ÂÂ Certification
CE, FCC class A
ÂÂ Dimensions
30 x 139 x 100 mm
(W x H x D)
ÂÂ Enclosure
ABS+PC
ÂÂ Weight
180 g
ÂÂ Connectors
2 x RJ-45 (2-channel
switch, share same IP
address)
ÂÂ Power Consumption 2 W @ 5 VDC (typical)
Communications
ÂÂ Protocol
EtherNet/IP
ÂÂ Connected I/O
32 (max.)*
Modules
ÂÂ Digital Signals
768 (max.)
ÂÂ Analog Signals
192 (max.)
ÂÂ Data Transfer Rates 10/100 Mbps
ÂÂ Topology
line or star
ÂÂ Isolation Protection 1,500 VAC
Environment
ÂÂ Operating
-10 ~ 60°C
Temperature
(mounted vertically)
 Storage Temperature -40 ~ 85°C
ÂÂ Relative Humidity 5 ~ 95% (non-condensing)
ÂÂ Shock Protection 10 G @ wall mount, half
sine, 11 ms (Confirms to
IEC 60068-2-27)
ÂÂ Vibration Protection 1 Grms @ 5 ~ 500 Hz
(Random, operating, 1 hr/
axis)
2 G @ 5 ~ 500 Hz (Sine,
non-operating, 1 hr/axis)
(Confirms to IEC 60068-2-
64 and IEC 60068-2-6)
Ordering Information
ÂÂ APAX-5072
EtherNet/IP Communication
Coupler
General
ÂÂ Certification
CE, FCC class A
ÂÂ Dimensions
30 x 139 x 100 mm
(W x H x D)
ÂÂ Enclosure
ABS+PC
ÂÂ Weight
180 g
ÂÂ Connector
2 x RJ-45 (2-channel
switch, share same IP
address)
ÂÂ Power Consumption 2 W @ 5 VDC (typical)
Communication
ÂÂ Protocol
PROFINET RT V2.2
ÂÂ Connected I/O
32 (max.)*
Modules
ÂÂ Digital Signals
768 (max.)
ÂÂ Analog Signals
192 (max.)
ÂÂ Data Transfer Rates 10/100 Mbps
ÂÂ APAX IO Topology Line or Star
Environment
ÂÂ Operating
-10 ~ 60°C
Temperature
(mounted vertically)
 Storage Temperature -40 ~ 85°C
ÂÂ Relative Humidity 5 ~ 95% (non-condensing)
ÂÂ Shock Protection 10 G @ wall mount, half
sine, 11 ms (Confirms to
IEC 60068-2-27)
ÂÂ Vibration Protection 1 Grms @ 5 ~ 500 Hz
(Random, operating, 1 hr/
axis)
2 G @ 5 ~ 500 Hz (Sine,
non-operating, 1 hr/axis)
(Confirms to IEC 60068-2-
64 and IEC 60068-2-6)
Ordering Information
ÂÂ APAX-5071
PROFINET Communication
Coupler
Accessories
ÂÂ APAX-5002
ÂÂ APAX-5343E
2-slot Backplane Module
Power Supply for APAX Expansion Module
*APAX DI/O modules can use ID number 0 ~ 31, while AI/O modules and counter modules can only use ID numbers 0 ~ 15
DIN-Rail IPCs
All product specifications are subject to change without notice
Last updated : 5-May-2015
|