English
Language : 

ADAM-5017_14 Datasheet, PDF (1/1 Pages) Advantech Co., Ltd. – 8-ch Ultra High Speed Analog Input Module
ADAM-5017UH
ADAM-5018
ADAM-5018P
8-ch Ultra High Speed Analog Input
Module
7-ch Thermocouple Input Module
7-ch Thermocouple Input Module
with Independent Input Range
ADAM-5017UH
RoHS
COMPLIANT
2002/95/EC
ADAM-5018
RoHS
COMPLIANT
2002/95/EC
ADAM-5018P
RoHS
COMPLIANT
2002/95/EC
Specifications
General
ƒƒ Certification
ƒƒ Connectors
ƒƒ Enclosure
ƒƒ Power Consumption
CE
1 x Plug-in screw terminal
(# 14 ~ 22 AWG)
ABS+PC
2.2 W (max.)
Analog Input
ƒƒ Accuracy
±0.1% or better
ƒƒ Bandwidth
200 kHz
ƒƒ Channels
8 differential
ƒƒ Differential Non-linear ±1 LSB
ƒƒ Input Impedance Voltage: 2 MΩ
Current: 120 Ω (Build-in)
ƒƒ Integral Non-linear ±1 LSB
ƒƒ Input Range
±10 V, +0 ~ 10 V,
0 ~ 20 mA, +4 ~ 20 mA
ƒƒ Low pass filter
Configured by User
ƒƒ Resolution
12-bit
ƒƒ Sampling Rate
Depends on base unit
ADAM-5000/485 & 5000E:
100 Samples/sec max (Total): one ADAM-5017UH
installed
ADAM-5000/TCP & 5000L/TCP:
100 Samples/sec max (Total) :one ADAM-5017UH
installed
ADAM-5510 :
200K Samples/sec max (Single Channel): one ADAM-
5017UH installed
ADAM-5550 & ADAM-5560:
1K Samples/sec max(single channel): one ADAM-
5017UH installed
*Depending on the performance of client server or
controller
ƒƒ Signal Input
200 kHz for both voltage
Bandwidth
and current inputs
Protection
ƒƒ Isolation Voltage
Note:
3,000 VDC
1) The voltage difference between any two pins must not
exceed 15 V
2) Distinct range settings allowed on each channel
Note: Not support ADAM-5510KW series
Ordering Information
ƒƒ ADAM-5017UH
8-ch Ultra High Speed
Analog Input Module
Specifications
General
ƒƒ Certification
CE, FM
ƒƒ Connectors
1 x Plug-in screw terminal
(# 14 ~ 22 AWG)
ƒƒ Enclosure
ABS+PC
ƒƒ Power Consumption 0.63 W (max.)
Thermocouple Input
ƒƒ Accuracy
±0.1% or better
ƒƒ Bandwidth
13.1 Hz @ 50 Hz
15.72 Hz @ 60 Hz
ƒƒ Channels
7 differential
ƒƒ CMR @ 50/60 Hz 92 dB min
ƒƒ Input Impedance 2 MΩ
ƒƒ lnput Range
±15 mV, ±50 mV, ±100 mV,
±500 mV,
±1 V, ±2.5 V, ±20 mA
ƒƒ lnput Type
mV, V, mA, thermocouple
ƒƒ Resolution
16-bit
ƒƒ Sampling Rate
10 samples/sec. (total)
ƒƒ Span Drift
±25 PPM/ °C
ƒƒ Zero Drift
±6 μV/ °C
ƒƒ T/C Type and Temperature Range
J
0°
~
760°C
K
0°
~
1,370°C
T
-100°
~
400°C
E
0°
~
1,000°C
R
500°
~
1,750°C
S
500°
~
1,750°C
B
500°
~
1,800°C
Protection
ƒƒ Fault and
Overvoltage
Protection
ƒƒ Isolation Voltage
Withstands overvoltage up
to ±35 V
3,000 VDC
Ordering Information
ƒƒ ADAM-5018
ƒƒ ADAM-5018SK
7-ch Thermocouple Input
Module
ADAM-5018 with CJC kit/
external
Specifications
General
ƒƒ Certification
CE, FCC class A
ƒƒ Connectors
1 x Plug-in screw terminal
(# 14 ~ 22 AWG)
ƒƒ Enclosure
ABS+PC
ƒƒ Power Consumption 0.63 W (max.)
Thermocouple Input
ƒƒ Accuracy
Voltage mode: ±0.1% or
better
Current mode: ±0.2% or
better
ƒƒ Bandwidth
13.1 Hz @ 50 Hz
15.72 Hz @ 60 Hz
ƒƒ Channels
7 (differential, each channel
can be configured with
different range)
ƒƒ CMR @ 50/60 Hz 92 dB min
ƒƒ Input Impedance 20 MΩ. (Build-in 120 Ω
Register for Current Input)
ƒƒ lnput Range and Types
Thermocouple
J
0
~
760°C
K
0
~
1,370°C
T
-100
~
400°C
E
0
~
1,000°C
R
500
~
1,750°C
S
500
~
1,750°C
B
500
~
1,800°C
Current
±20 mA, 4 ~ 20 mA
Voltage
±15 mV (0.2%), ±50 mV,
±100 mV, ±500 mV
±1 V, ±2.5 V
ƒƒ Resolution
16-bit
ƒƒ Sampling Rate
10 samples/sec. (total)
ƒƒ Span Drift
±25 PPM/°C
ƒƒ Zero Drift
±6 μV/°C
ƒƒ High Common Mode 200 VDC
Protection
ƒƒ Fault and
Withstands overvoltage up
Overvoltage
to ±35 V
Protection
ƒƒ Isolation Voltage 3,000 VDC
ƒƒ Filter function
Yes
ƒƒ Built-in TVS/ESD Protection
Note: Not support ADAM-5510KW series
Ordering Information
ƒƒ ADAM-5018P
7-ch Thermo. Input Module
w/ Ind. Input Range
Programmable Automation Controllers
All product specifications are subject to change without notice
Last updated : 28-Aug-2013