ADAM-4118 Datasheet, PDF (1/1 Pages) Advantech Co., Ltd. – Robust 8-ch Thermocouple Input Module with Modbus | |||
|
ADAM-4118
ADAM-4150
ADAM-4168
Robust 8-ch Thermocouple Input Module with
Modbus
Robust 15-ch Digital I/O Module with Modbus
Robust 8-ch Relay Output Module with Modbus
ADAM-4118
RoHS
COMPLIANT
2002/95/EC
Specifications
General
ï§ Power Consumption 0.5W @ 24 VDC
Analog Input
ï§ Channels
8 differential and
independent configuration
channels
ï§ Input Impedance Voltage: 20 Mâ¦
Current: 120 â¦
ï§ Input Type
T/C, mV, V, mA
ï§ Input Range
Thermocouple
J 0 ~ 760° C
K 0 ~ 1370° C
T -100 ~ 400° C
E 0 ~ 1,000° C
R 500 ~ 1,750° C
S 500 ~ 1,750° C
B 500 ~ 180° C
Voltage mode
±15 mV, ±50 mV,
±100 mV, ±500 mV,
±1 V, ±2.5 V
Current mode
±20 mA, 4 ~ 20 mA
ï§ Accuracy
Voltage mode: ±0.1% or
better
Current mode: ±0.2% or
better
ï§ Resolution
16-bit
ï§ Sampling Rate
10/100 samples/sec
(selected by Utility)
ï§ CMR @ 50/60 Hz 92 dB
ï§ NMR @ 50/60 Hz 60 dB
ï§ Overvoltage Protection
±60 VDC
ï§ High Common Mode 200 VDC
ï§ Span Drift
±25 ppm/° C
ï§ Zero Drift
±6μV/° C
ï§ Built-in TVS/ESD Protection
ï§ Burn-out Detection
ADAM-4150
RoHS
COMPLIANT
2002/95/EC
Specifications
General
ï§ Power Consumption 0.7 W @ 24 VDC
Digital Input
ï§ Channels
7
ï§ Input Level
Dry contact:
Logic level 0: Close to
GND
Logic level 1: Open
Wet contact:
Logic level 0: +3 V max
Logic level 1: +10 V to
+30 V
(Note: The Digital Input Level 0 and 1 status can be
inverted)
ï§ Supports 3 kHz Counter Input (32-bit + 1-bit
overflow)
ï§ Supports 3 kHz Frequency Input
ï§ Supports Invert DI Status
ï§ Over Voltage
40 VDC
Digital Output
ï§ Channels
8, open collector to 40 V
(1 A max. load)
ï§ Power Dissipation 1W load max
ï§ RON Maximum
150 mâ¦
ï§ Supports 1 kHz Pulse Output
ï§ Supports High-to-Low Delay Output
ï§ Supports Low-to-High Delay Output
ADAM-4168
RoHS
COMPLIANT
2002/95/EC
Specifications
General
ï§ Power Consumption 1.8 W @ 24 VDC
Relay Output
ï§ Output Channels 8 Form A
ï§ Contact Rating
AC:
(Resistive)
DC:
0.5 A @ 120 V
0.25 A @ 240 V
1 A @ 30 V
0.3 A @ 110 V
ï§ Breakdown Voltage 750 VAC (50/60 Hz)
ï§ Initial Insulation 1 G ⦠min. @ 500 VDC
Resistance
ï§ Relay Response
Time (Typical)
On: 3ms
Off: 1ms
ï§ Total Switching Time 10 ms
ï§ Supports 100 Hz pulse output
ï§ Maximum Operating 50 operations/min
Speed
(at related load)
Ordering Information
ï§ ADAM-4118
ï§ ADAM-4150
ï§ ADAM-4168
Robust 8-ch
Thermocouple Input
Module w/ Modbus
Robust 15-ch Digital I/O
Module with Modbus
Robust 18-ch Relay
Output Module with
Modbus
Common Specifications
ï§ Power Input
ï§ Watchdog Timer
ï§ Connector
ï§ Isolation Voltage
ï§ Supported Protocols
Unregulated 10 ~ 48 VDC
System (1.6 second) &
Communication
2 x plug-in terminal
blocks (#14 ~ 22 AWG)
3,000 VDC
ASCII Command and
Modbus/RTU
Environment
ï§ Humidity
5 ~ 95% RH
ï§ Operating Temperature -40 ~ 85° C
(-40 ~ 185° F)
ï§ Storage Temperature -40 ~ 85° C
(-40 ~ 185° F)