English
Language : 

ADAM-4080_15 Datasheet, PDF (1/1 Pages) Advantech Co., Ltd. – 2-ch Counter/Frequency Module
ADAM-4055
16-ch Isolated Digital I/O Module with
Modbus
ADAM-4056S/4056SO 12-ch Sink/Source Type Isolated Digital
Output Modules with Modbus
ADAM-4080
2-ch Counter/Frequency Module
ADAM-4055
RoHS
COMPLIANT
2002/95/EC
Specifications
General
ƒƒ Connectors
2 x plug-in terminal blocks
(#14 ~ 28 AWG)
ƒƒ Power Consumption 1 W @ 24 VDC
ƒƒ Watchdog Timer System (1.6 second) &
Communication
ƒƒ Supported Protocols ASCII command and
Modbus/RTU
ƒƒ Isolation Voltage 2,500 VDC
ƒƒ LED Indicators
Yes
Digital Input
ƒƒ Channels
ƒƒ Input Level
Dry Contact:
Wet Contact:
ƒƒ Overvoltage
Protection
8
Logic level 0: open
Logic level 1: close to GND
Logic level 0: 3 V max.
Logic level 1: 10 ~ 50 V
70 VDC
Digital Output
ƒƒ Channels
ƒƒ Power Dissipation
8, open collector to 40 V
(200 mA max. load)
Channel: 1 W max.
Total: 2.2 W (8 Channels)
Common Specifications
General
ƒƒ Power Input
Unregulated 10 ~ 30 VDC
Environment
ƒƒ Operating Humidity 5 ~ 95% RH
ƒƒ Operating
Temperature
-10 ~ 70°C
(14 ~ 158°F)
ƒƒ Storage Temperature -25 ~ 85°C
(-13 ~ 185°F)
ADAM-4056S/4056SO
RoHS
COMPLIANT
2002/95/EC
Specifications
General
ƒƒ Connectors
ƒƒ Watchdog Timer
ƒƒ Support Protocol
ƒƒ Isolation Voltage
ƒƒ LED Indicators
2 x Plug-in terminal blocks
(#14~22 AWG)
System (1.6 second) &
Communication
ASCII command and
Modbus/RTU
5000 VDC
Yes
ADAM-4056S
ƒƒ Digital Output
Channels
ƒƒ Power Dissipation
ƒƒ Digital Output Type
12
Open collector to 40V
(200mA max. load)
Channel: 1 W max
Total: 4 W
(12 Channels)
Sink
ADAM-4056SO
ƒƒ Digital Output
Channels
12
VCC: 10 ~ 35 VDC
Current: 1A
(per channel)
ƒƒ Digital Output Type Source
ƒƒ Over Current Detection and Protection
Ordering Information
ƒƒ ADAM-4055
ƒƒ ADAM-4056S
ƒƒ ADAM-4056SO
ƒƒ ADAM-4080
16-ch Isolated Digital I/O
Module with Modbus
12-ch Sink Type Isolated
Digital Output Module
with Modbus
12-ch Source Type
Isolated Digital Output
Module with Modbus
2-ch Counter/Frequency
Modules
ADAM-4080
RoHS
COMPLIANT
2002/95/EC
Specifications
General
ƒƒ Connectors
2 x plug-in terminal blocks
(#14 ~ 22 AWG)
ƒƒ Power Consumption 2.0 W @ 24 VDC
ƒƒ Watchdog Timer System (1.6 second)
ƒƒ Supported Protocols ASCII command
Counter Input
ƒƒ Channels
2 independent counters
(32-bit + 1-bit overflow)
ƒƒ Input Frequency 50 kHz max.
ƒƒ Input Pulse Width >10 μs.
ƒƒ Input Mode
lsolated or non-isolated
ƒƒ Isolated Input Level Logic level 0: 1 V max.
Logic level 1: 3.5~30 V
ƒƒ Isolation Voltage
ƒƒ Non-isolated
Input Level
2,500 VRMS
Programmable
threshold:
Logic level 0: 0.8 Vmax.
Logic level 1: 2.4 ~ 5.0 V
ƒƒ Maximum Count 4,294,967,295 (32-bit)
ƒƒ Preset Type
Absolute or relative
ƒƒ Programmable
2 μs ~ 65 ms
Digital Noise Filter
ƒƒ Alarm
Alarm comparators on each
counter
ƒƒ Frequency
5 Hz ~ 50 kHz
Measurement Range
ƒƒ Programmable
1 or 0.1 second
Built-in Gate Time
Digital Output
ƒƒ Channels
ƒƒ Power Dissipation
2, open collector to 30 V,
30 mA max. load
300 mW for each channel
All product specifications are subject to change without notice
Online Download www.advantech.com/products