ADAM-4080 Datasheet, PDF (1/1 Pages) Advantech Co., Ltd. – 2-ch Counter/Frequency Modules (with 7-segment LED Display) | |||
|
ADAM-4080/4080D
ADAM-4914V
2-ch Counter/Frequency
Modules (with
7-segment LED Display)
4-ch Voltage Input Surge
Protection Module
ADAM-4080/4080D
Specifications
General
ï§ Connectors
ï§ Power Consumption
ï§ Power Input
ï§ Humidity
ï§ Operating Temperature
ï§ Storage Temperature
ï§ Watchdog Timer
ï§ Support Protocol
ï§ LED Indicators
2 x Plug-in terminal block (#14 ~ 22 AWG)
2.0 W @ 24 VDC
Unregulated 10 ~ 30 VDC
5 ~ 95% RH
-10 ~ 70° C (14 ~ 158° F )
-25 ~ 85° C (-13 ~ 185° F)
System (1.6 second)
ASCII command
5-digit readout, CH 0 or CH 1 (programmable)
(ADAM-4080D only)
Counter Input
ï§ Channels
ï§ Input Frequency
ï§ Input Pulse Width
ï§ Input Mode
ï§ Isolated Input Level
ï§ Isolation Voltage
ï§ Non-isolated
Input Level
ï§ Maximum Count
ï§ Preset Type
ï§ Programmable Digital
Noise Filter
ï§ Alarm
2 independent 32-bit counters
50 kHz max.
(non-isolation)
>10 μs.
lsolated or non-isolated
Logic level 0: +1 V max.
Logic level 1: 3.5~30 V
2500 VRMS
Programmable threshold:
Logic level 0: +0.8 V max.
Logic level 1: 2.4 ~ 5.0 V
4,294,967,295 (32 bits)
Absolute or relative (ADAM-4080 only)
2 μs ~ 65 ms
ADAM-4080: Alarm comparators on each counter
ADAM-4080D: High and Low comparators on counter 0
Frequency Measurement
ï§ Range
5 Hz ~ 50 kHz
ï§ Programmable Built-in 1 or 0.1 second
Gate Time
Digital Output
ï§ Channels
ï§ Open Collector
ï§ Power Dissipation
2
30 V, 30 mA max. load
300 mW for each channel
ADAM-4914V
Specifications
General
ï§ Connectors
2 x Plug-in terminal block (#14 ~ 22 AWG)
ï§ Humidity
5 ~ 95% RH
ï§ Operating Temperature -10 ~ 70° C (14 ~ 158° F)
ï§ Storage Temperature -25 ~ 85° C (-13 ~ 185° F)
ï§ Input Channels
4 differential voltage and thermocouple input
Performance
ï§ Discharge Current 5000 A (8/20 µsec.)
ï§ Discharge Voltage Between Lines: 18 V min.
Line to GND: 350 V max.
ï§ Internal Series
Resistance
Approx. 20 ⦠including
return
ï§ Max. Surge Voltage Between Lines: 23 V min.
Line to GND: +4,000 V max.
ï§ Leakage Current
Between Lines: ⤠10 µA @ 7.5 VDC
Line to GND: ⤠5 µA @ +140 VDC
ï§ Maximum Line Voltage 10 V
ï§ Response Time
⤠0.1 µsec.
Ordering Information
ï§ ADAM-4080/4080D
ï§ ADAM-4914V
2-ch Counter/Frequency Modules
(with 7-segment LED Display)
4-ch Voltage Input Surge Protection Module
Online Download www.advantech.com/products
|