3B20 Datasheet, PDF (4/8 Pages) Analog Devices – AC Strain Gage, Torque Transducer Input
Zero Calibration Adjustment Range4
Phase Adjustment Range5
Input Bias Current
Input Resistance
Bandwidth, -3 dB
Output Rise Time, 10% to 90% Span
±1 V, minimum
0 to 4.25° minimum @ 1 kHz
0 to 14° minimum @ 3.28 kHz
0 to 37.25° minimum @ 10 kHz
+10 nA
100 MΩ
100 Hz
200 ms
3B20
Input Protection, Signal and Excitation Voltage
Continuous
130 V rms maximum
Transient
ANSI/IEEE C37.90.1-1989
Voltage Output Protection
Continuous Short to Ground
Current Output Protection
130 V rms, continuous
Power Supply Voltages 5
±15 V dc Supplies
Rated Operation
±(13 V dc to 18 V dc)
Current
±65 mA
Sensitivity
±0.03% span/V
+24 V dc Loop Supply
Rated Operation
+13.5 V dc to +30 V dc
Current
Sensitivity
+27 mA @ lout = 20 mA
±0.001% span/V
Mechanical Dimensions
3.15" x 3.395" x 0.775"
(80.0 mm x 86.2 mm x 19.7 mm)
Environmental
Temperature Range
Rated Performance
-25°C to +85°C
Storage
-55°C to +85°C
Relative Humidity, 24 hours
0 to 95% @ +60°C non-condensing
RFI Susceptibility
±0.5% Span error @ 400 MHz, 5 Watt, 3 ft
1 For a 0 mA to 20 mA range, a typical minimum output current is 10 µA.
2 Includes the combined effects of repeatability, hysteresis, and nonlinearity.
3 With respect to the voltage output.
4 A wide range of custom zero suppression and span is available with the 3B20-00 model, using the AC1310 ranging card.
5 +24 V dc loop power is required for driving the current output at loads up to 850Ω. If a current output load of 400Ω or less is applied, +15 V dc is sufficient for loop power. If only
voltage output is used, loop power is not required.
Specifications subject to change without notice.
Rev. 0 | Page 4 of 8