L-11-10-P Datasheet, PDF (3/4 Pages) Analog Devices – 11-2S-P thru 13-500-P Ring Tongue, Vinyl Insulated, Butted Seam
Installation Information
ƽ WARNING
Turn power off before installing or removing terminal. All electrical
work should be done according to appropriate electrical codes.
UL Listed and CSA Certified for use on stranded copper
(AWG) wire only.
Strip away the end 3/8 inch of wire insulation.
Make the crimp in the proper station of a recommended
3M crimp tool: TH-440, TH-450 (scissor style), or
TR-490 (ratchet style) hand tools.
Barrel Crimp (Electrical)
Engineering Specification
Crimp-type terminals shall, electrically and
mechnically, connect to a pre-stripped end of a
stranded copper wire and have a flat tongue portion
with a central opening for mounting around a screw or
stud.
The terminal line shall offer tongue variations in hole
(stud) size (6, 8 10, etc.) and configuration (ring, fork,
block fork, flanged block fork, locking fork, etc.): and
barrel variations in wire (AWG) size (22-18, 16-14,
12-10, etc.) and construction (non-insulated brazed
seam, vinyl insulated butted seam, nylon insulated
with insulation grip, etc.). The terminal line shall have
regulatory agency coverage (UL Listing, CSA
Certification). The terminal tongue shall be marked
with the wire range and manufacturer’s symbol ( ).
The vinyl-insulated, butted seam ring tongue terminal
shall be tin-plated, annealed copper, with the tongue
having a specified stud hole (size 2 thru 1/2 in.) and a
butted seam barrel covered by a molded vinyl funnel
entry sleeve, color coded and sized for a specified
(AWG) wire range (22-18, 16-14, 12-10).
Insulated terminals shall be UL Listed and CSA
Certified for 600 Volts maximum building wire: 1000
Volts maximum in signs, fixtures and luminaries and
have a maximum operating temperature of 221°F
(105°C).